5 retailersCalculate the voltage drop across DC cable runs in your off-grid energy system. Essential for ensuring your cables are correctly sized and your equipment receives adequate voltage.
Enter your values and click Calculate to see results.
Voltage drop occurs in all electrical cables due to the resistance of the conductor material. For DC systems, this is calculated using:
Vdrop = (2 × L × I × ρ) / A
Where: L = cable length (one way, metres), I = current (Amps), ρ = resistivity of copper (0.0175 Ω·mm²/m), A = cable cross-section area (mm²)
The factor of 2 accounts for the return path (positive and negative cables).
For inverters and chargers, keeping voltage drop below 3% is strongly recommended to ensure optimal performance and to avoid low-voltage alarms.